Bedoukian   RussellIPM   RussellIPM   Piezoelectric Micro-Sprayer


Home
Animal Taxa
Plant Taxa
Semiochemicals
Floral Compounds
Semiochemical Detail
Semiochemicals & Taxa
Synthesis
Control
Invasive spp.
References

Abstract

Guide

Alphascents
Pherobio
InsectScience
E-Econex
Counterpart-Semiochemicals
Print
Email to a Friend
Kindly Donate for The Pherobase

« Previous AbstractInfluence of combined dust reducing carpet and compact air filtration unit on the indoor air quality of a classroom    Next Abstract"Assessment of exposure of gas station attendants in Sri Lanka to benzene, toluene and xylenes" »

Int J Environ Res Public Health


Title:Chemical Characterization of the Indoor Air Quality of a University Hospital: Penetration of Outdoor Air Pollutants
Author(s):Scheepers PTJ; Van Wel L; Beckmann G; Anzion RBM;
Address:"Research Lab Molecular Epidemiology, Radboud Institute for Health Sciences, Radboudumc, P.O. Box 9101, 6500 HB Nijmegen, The Netherlands. paul.scheepers@radboudumc.nl. Research Lab Molecular Epidemiology, Radboud Institute for Health Sciences, Radboudumc, P.O. Box 9101, 6500 HB Nijmegen, The Netherlands. luuk.vanwel@uu.nl. Institute for Risk Assessment Sciences (IRAS), Utrecht University, Yalelaan 2, 3584 CM Utrecht, The Netherlands. luuk.vanwel@uu.nl. Research Lab Molecular Epidemiology, Radboud Institute for Health Sciences, Radboudumc, P.O. Box 9101, 6500 HB Nijmegen, The Netherlands. gwendolyn.beckmann@radboudumc.nl. Research Lab Molecular Epidemiology, Radboud Institute for Health Sciences, Radboudumc, P.O. Box 9101, 6500 HB Nijmegen, The Netherlands. rob.anzion@radboudumc.nl"
Journal Title:Int J Environ Res Public Health
Year:2017
Volume:20170508
Issue:5
Page Number: -
DOI: 10.3390/ijerph14050497
ISSN/ISBN:1660-4601 (Electronic) 1661-7827 (Print) 1660-4601 (Linking)
Abstract:"For healthcare centers, local outdoor sources of air pollution represent a potential threat to indoor air quality (IAQ). The aim of this study was to study the impact of local outdoor sources of air pollution on the IAQ of a university hospital. IAQ was characterized at thirteen indoor and two outdoor locations and source samples were collected from a helicopter and an emergency power supply. Volatile organic compounds (VOC), acrolein, formaldehyde, nitrogen dioxide (NO(2)), respirable particulate matter (PM-4.0 and PM-2.5) and their respective benz(a)pyrene contents were determined over a period of two weeks. Time-weighted average concentrations of NO(2) (4.9-17.4 mug/m(3)) and formaldehyde (2.5-6.4 mug/m(3)) were similar on all indoor and outdoor locations. The median concentration VOC in indoor air was 119 mug/m(3) (range: 33.1-2450 mug/m(3)) and was fivefold higher in laboratories (316 mug/m(3)) compared to offices (57.0 mug/m(3)). PM-4.0 and benzo(a)pyrene concentration were lower in buildings serviced by a >99.95% efficiency particle filter, compared to buildings using a standard 80-90% efficiency filter (p < 0.01). No indications were found that support a significant contribution of known local sources such as fuels or combustion engines to any of the IAQ parameters measured in this study. Chemical IAQ was primarily driven by known indoor sources and activities"
Keywords:"Air Pollutants/*analysis Air Pollution/*analysis Air Pollution, Indoor/analysis Environmental Monitoring Formaldehyde/analysis *Hospitals, University Particulate Matter/analysis Volatile Organic Compounds/analysis acrolein benz(a)pyrene diesel engine exha;"
Notes:"MedlineScheepers, Paul T J Van Wel, Luuk Beckmann, Gwendolyn Anzion, Rob B M eng Switzerland 2017/05/10 Int J Environ Res Public Health. 2017 May 8; 14(5):497. doi: 10.3390/ijerph14050497"

 
Back to top
 
Citation: El-Sayed AM 2024. The Pherobase: Database of Pheromones and Semiochemicals. <http://www.pherobase.com>.
© 2003-2024 The Pherobase - Extensive Database of Pheromones and Semiochemicals. Ashraf M. El-Sayed.
Page created on 27-12-2024