Bedoukian   RussellIPM   RussellIPM   Piezoelectric Micro-Sprayer


Home
Animal Taxa
Plant Taxa
Semiochemicals
Floral Compounds
Semiochemical Detail
Semiochemicals & Taxa
Synthesis
Control
Invasive spp.
References

Abstract

Guide

Alphascents
Pherobio
InsectScience
E-Econex
Counterpart-Semiochemicals
Print
Email to a Friend
Kindly Donate for The Pherobase

« Previous AbstractIndoor air-related symptoms and volatile organic compounds in materials and air in the hospital environment    Next AbstractThe early transcriptome response of cassava (Manihot esculenta Crantz) to mealybug (Phenacoccus manihoti) feeding »

Int J Environ Health Res


Title:"Emissions, airflow patterns and modeling of test compounds in controlled hospital environments"
Author(s):Rautiainen P; Ruokolainen J; Saarinen P; Pasanen P; Hyttinen M;
Address:"Department of Building Management, Kuopio University Hospital, Kuopio, Finland. Department of Environmental and Biological Sciences, University of Eastern Finland, Kuopio, Finland. Engineering and Business, Turku University of Applied Sciences, Turku, Finland"
Journal Title:Int J Environ Health Res
Year:2021
Volume:20190827
Issue:4
Page Number:374 - 388
DOI: 10.1080/09603123.2019.1657562
ISSN/ISBN:1369-1619 (Electronic) 0960-3123 (Linking)
Abstract:"Spreading and distribution of selected volatile organic compounds (VOCs) released as point source emissions in a hospital environment were investigated in two office rooms and two patient rooms. Six tracer compounds were released from six locations and their concentrations were measured in five sampling sites during two consecutive days. The air flow rates, velocity and flow direction, air temperature, pressure differences between adjacent rooms, and relative humidity and concentrations of the tracer compounds were measured. The results revealed that the size of the examined space and ventilation rates, the monitoring point should be either close to the exhaust terminal device or in the middle of the occupied zone the way that supply air flows do not interfere the measurements. Depending on the inlet terminal device and its location, the air is either delivered parallel to the ceiling or it can be directed to a desired spot into the occupied zone. The tracer compounds did spread evenly within the room and their concentrations decreased inversely with the distance. In rooms with a good ventilation, the concentrations at the exhaust air terminal units were close to those measured near the source point. The results obtained from modeling were consistent with the measurements"
Keywords:"*Air Movements Air Pollutants/*analysis Air Pollution, Indoor/*analysis *Hospitals Models, Theoretical Ventilation/*statistics & numerical data Volatile Organic Compounds/*analysis Volatile organic compounds (VOCs) air distribution model compounds modelli;"
Notes:"MedlineRautiainen, Paavo Ruokolainen, Joonas Saarinen, Pekka Pasanen, Pertti Hyttinen, Marko eng England 2019/08/29 Int J Environ Health Res. 2021 Jun; 31(4):374-388. doi: 10.1080/09603123.2019.1657562. Epub 2019 Aug 27"

 
Back to top
 
Citation: El-Sayed AM 2024. The Pherobase: Database of Pheromones and Semiochemicals. <http://www.pherobase.com>.
© 2003-2024 The Pherobase - Extensive Database of Pheromones and Semiochemicals. Ashraf M. El-Sayed.
Page created on 26-12-2024