Bedoukian   RussellIPM   RussellIPM   Piezoelectric Micro-Sprayer


Home
Animal Taxa
Plant Taxa
Semiochemicals
Floral Compounds
Semiochemical Detail
Semiochemicals & Taxa
Synthesis
Control
Invasive spp.
References

Abstract

Guide

Alphascents
Pherobio
InsectScience
E-Econex
Counterpart-Semiochemicals
Print
Email to a Friend
Kindly Donate for The Pherobase

« Previous AbstractIdentification of the volatile profiles of 22 traditional and newly bred maize varieties and their porridges by PTR-QiTOF-MS and HS-SPME GC-MS    Next AbstractInternational studies to compare methods for personal sampling of bitumen fumes »

Indian J Occup Environ Med


Title:Etiological investigation of unintentional solvent exposure among university hospital staffs
Author(s):Ekpanyaskul C;
Address:"Department of Preventive and Social Medicine, Faculty of Medicine, Srinakharinwirot University, 114 Sukhumvit 23, Wattana, Bangkok, Thailand"
Journal Title:Indian J Occup Environ Med
Year:2010
Volume:14
Issue:3
Page Number:100 - 103
DOI: 10.4103/0019-5278.75699
ISSN/ISBN:1998-3670 (Electronic) 0973-2284 (Print) 0973-2284 (Linking)
Abstract:"AIM: This study was done to investigate unintentional solvent exposure in Srinakharinwirot university hospital staffs with unknown etiology. MATERIAL AND METHODS: A multidisciplinary investigation was conducted. Total volatile organic compounds (TVOCs) in working environments were measured. Biomarkers of exposure and self-administered questionnaires about clinical symptoms were collected, during and after the incidence, from the affected workers. RESULTS: The reason behind this event was found to be renovation of the 15(th) floor. TVOCs contaminated the air hanging unit of the lower 5th floor via space of the pipeline system of the building. The average TVOC value in the complaint area, on the date of notification, was 9.5 ppm. The symptoms and level of hippuric acid, collected during the incidence, were significantly higher than those collected after the problems were solved. CONCLUSIONS: The solvent from the renovation site was a potential source of health hazards for hospital staffs. The relevant authorities should be concerned about implementing a policy for the prevention of indoor pollution in the hospital"
Keywords:Building-related illness hospital indoor environmental quality indoor pollution solvent;
Notes:"PubMed-not-MEDLINEEkpanyaskul, Chatchai eng India 2011/04/05 Indian J Occup Environ Med. 2010 Sep; 14(3):100-3. doi: 10.4103/0019-5278.75699"

 
Back to top
 
Citation: El-Sayed AM 2024. The Pherobase: Database of Pheromones and Semiochemicals. <http://www.pherobase.com>.
© 2003-2024 The Pherobase - Extensive Database of Pheromones and Semiochemicals. Ashraf M. El-Sayed.
Page created on 22-11-2024