|
Int J Environ Res Public Health
Title: | Effects of Ventilation Improvement on Measured and Perceived Indoor Air Quality in a School Building with a Hybrid Ventilation System |
|
Author(s): | Vornanen-Winqvist C; Salonen H; Jarvi K; Andersson MA; Mikkola R; Marik T; Kredics L; Kurnitski J; |
|
Address: | "Department of Civil Engineering, Aalto University, Rakentajanaukio 4, 02150 Espoo, Finland. camilla.vornanen@aalto.fi. Department of Civil Engineering, Aalto University, Rakentajanaukio 4, 02150 Espoo, Finland. heidi.salonen@aalto.fi. Department of Civil Engineering, Aalto University, Rakentajanaukio 4, 02150 Espoo, Finland. kati.jarvi@aalto.fi. Department of Civil Engineering, Aalto University, Rakentajanaukio 4, 02150 Espoo, Finland. maria.a.andersson@helsinki.fi. Department of Civil Engineering, Aalto University, Rakentajanaukio 4, 02150 Espoo, Finland. raimo.mikkola@aalto.fi. Department of Microbiology, University of Szeged, Kozep fasor 52, H-6726 Szeged, Hungary. mariktamas88@gmail.com. Department of Microbiology, University of Szeged, Kozep fasor 52, H-6726 Szeged, Hungary. kredics@bio.u-szeged.hu. Department of Civil Engineering, Aalto University, Rakentajanaukio 4, 02150 Espoo, Finland. jarek.kurnitski@aalto.fi. Department of Civil Engineering and Architecture, Tallinn University of Technology, Ehitajate tee 5, 19086 Tallinn, Estonia. jarek.kurnitski@aalto.fi" |
|
Journal Title: | Int J Environ Res Public Health |
Year: | 2018 |
Volume: | 20180705 |
Issue: | 7 |
Page Number: | - |
DOI: | 10.3390/ijerph15071414 |
|
ISSN/ISBN: | 1660-4601 (Electronic) 1661-7827 (Print) 1660-4601 (Linking) |
|
Abstract: | "Ventilation system design and operation may significantly affect indoor air quality (IAQ). The aims of this case study were to investigate the functionality of a supply air fan-assisted hybrid ventilation system in a newly built school building with reported IAQ problems and to determine the effects of ventilation improvement on measured and perceived IAQ. The ventilation system function was researched simultaneously with IAQ measurements, with an analysis of total volatile organic compounds (TVOC), single volatile organic compounds (VOCs), and indoor mycobiota, and with questionnaires about perceived IAQ. At the baseline, an operational error of the ventilation system was found, which prevented the air from coming into the classrooms, except for short periods of high carbon dioxide (CO(2)) concentrations. After the ventilation operation was improved, a significant change in indoor mycobiota was found; the dominant, opportunistic human pathogenic species Trichoderma citrinoviride found in settled dust in the classroom before the improvement was no longer detected. In addition, the concentrations of CO(2), TVOC, and some single VOCs, especially toluene and decamethylcyclopentasiloxane, decreased. The analysis of the questionnaire results indicated that the perceptions of unpleasant odors and stuffy air decreased, although a statistically significant improvement in perceived IAQ was not observed. The results provided evidence that the properly controlled hybrid ventilation system operating in mechanical supply mode provided adequate ventilation and was effective in decreasing the concentrations of some indoor-generated pollutants. With simple ventilation adjustments, microbiological exposure from building structures might be prevented" |
|
Keywords: | "Air Microbiology/standards Air Pollutants/*analysis Air Pollution, Indoor/*analysis Child Environmental Exposure/*analysis Environmental Monitoring Humans *Schools Trichoderma/isolation & purification Ventilation/instrumentation/*standards Trichoderma cit;" |
|
Notes: | "MedlineVornanen-Winqvist, Camilla Salonen, Heidi Jarvi, Kati Andersson, Maria A Mikkola, Raimo Marik, Tamas Kredics, Laszlo Kurnitski, Jarek eng Research Support, Non-U.S. Gov't Switzerland 2018/07/07 Int J Environ Res Public Health. 2018 Jul 5; 15(7):1414. doi: 10.3390/ijerph15071414" |
|
|
|
|
|
Citation: El-Sayed AM 2024. The Pherobase: Database of Pheromones and Semiochemicals. <http://www.pherobase.com>.
© 2003-2024 The Pherobase - Extensive Database of Pheromones and Semiochemicals. Ashraf M. El-Sayed.
Page created on 19-12-2024
|